R-KEY-LT

$189.00

1-port ModBUS-RTU/ASCII industrial gateway

 

R-KEY-LT is a compact and robust Modbus gateway that converts from Modbus TCP-IP protocol to Modbus RTU/ASCII and vice versa. It supports up to 8 Modbus TCP-IP clients at the same time, with up to 10 Modbus TCP-IP servers. With this model, serial Modbus slave devices can be integrated into an existing Modbus TCP-IP network, as well as Modbus TCP-IP slave devices can be made accessible to serial masters. R-KEY-LT can be configured via web server and software. It has Vac/dc power supply on the same hardware, insulation 1.5 kVac, extended temperature range. The device can also be powered via a 12V o 24V power supply unit.

Description

TECHNICAL DATA

POWER SUPPLY 10..40 Vdc; 19..28 Vac
POWER CONSUMPTION ~1 W
INSULATION 1,5 kVac
LED STATUS INDICATORS Power supply
Rx-Tx serial communication
Ethernet Link and data transfer
CONNECTIONS Morsetti a vite estraibili a 7/2 vie, passo 5 mm
ETHERNET PORT Nr 1 fast Ethernet port 100 Tx, RJ45 (max 8 Client TCP-IP / max 10 Server TCP/IP)
SERIAL PORT Nr 1 serial port RS232/RS485 commutable, baud rate max 115k
INDUSTRIAL PROTOCOLS SUPPORTED ModBUS TCP-IP, ModBUS RTU, ModBUS ASCII
MODBUS BRIDGE FUNCTION from ModBUS TCP-IP to Modbus RTU/ASCII
from ModBUS RTU/ASCII to Modbus TCP-IP
DATA SNIFFER ON SERIAL PORT Yes, via webserver
CONFIGURATION Via DIP-switch or Webserver
FIRMWARE UPGRADE Via Web Server
INSTALLATION DIN guide (IEC EN 60715)
PROTECTION DEGREE IP20
OPERATING TEMPERATURE -25..+70°C
DIMENSION (WXHXD) 53x90x32 mm
WEIGHT 80 g
CERTIFICATION CE