– 8 universal analog input channels:
Thermocouples, V, mV, mA, Pt100 and Pt1000
Reading and logging rates of up to 1000/second
24-bit A/D conversion resolution
– 8 digital I/Os (individually configured as input or output)
– 2 relay outputs (NO, NC and common)
– RS485 interface (Modbus master or slave)
When acting as a master, can read up to 64 registers from other slaves
Registers read can be used in logging, alarms, or mathematical operations
– Ethernet interface with a lot of services available:
Sends alarm warning e-mails (SMTP)
Provides web pages with channels and status information (HTTP);
Allows logged data download via FTP (client and server)
Accesses status and channels values through network management software (SNMP and traps)
Allows Modbus communication by ethernet interface (Modbus TCP)
– USB-device interface for configuring, monitoring and download
– USB-host interface for logged data retrieval through a USB flash drive
– Up to 32 configurable alarms:
Alarm actions can include: activating relays, activating digital outputs, emails sending to multiple receivers, sending SNMP traps, starting and/or stopping logging.
– Up to 128 virtual channels:
– Basic mathematical functions to be applied on other channels: sum, subtraction, multiplication, division, logic (AND, OR and exclusive OR), square root, and power
– Auxiliar power supply 24 Vdc for up to eight 4-20 mA transmitters
– Power Supply
AC power (100 to 240 Vac)
DC Power (19 to 30 Vdc) optional (2011)
– Detachable human-machine interface (optional)
Keypad and color TFT QVGA display
RS485 communication with FieldLogger
– Loggings:
Up to 100 channels can be logged at a configurable rate
Data download through the configuration software or through the freely distributed download DLL
– UL and CE compliant